ATLANTA– The newly published 2013 version of ASHRAE’s residential indoor air quality standard removes the default leakage rate assumption and also requires carbon monoxide alarms.
ANSI/ASHRAE Standard 62.2-2013, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings, is the only nationally recognized indoor air quality standard developed solely for residences. It defines the roles of and minimum requirements for mechanical and natural ventilation systems and the building envelope intended to provide acceptable indoor air quality in low-rise residential buildings.
One of the biggest changes in the standard over the 2010 version was an increase in mechanical ventilation rates to 7.5 cfm per person plus 3 cfm per 100 square feet. This is due to the earlier removal of the earlier default assumption regarding natural infiltration.
The Standard 62.2 Committee had previously assumed homes got a minimum of 2 cfm, per 100 square feet, according to Don Stevens, committee chair.
“Because research shows houses have gotten tighter and apartments have always been tight, the 2013 edition drops this default assumption and calls for the entire amount to be provided mechanically,” he said. “The only exception is when single family homes have a blower door test – then the predicted average annual leakage rate can be deducted.”
Another major change is a requirement for carbon monoxide (CO) alarms in all dwelling units. CO poisoning leads to hundreds of deaths and thousands of injuries each year in homes, resulting from automobiles left running in attached garages as well as from portable generators, power tools and heaters, according to Paul Francisco, committee vice chair. A small fraction of poisonings also result from failed central heating combustion appliances.
“Residents have very little ability to sense the presence of CO without detectors, unlike many other indoor polluting events,” he said.
Whether to include CO alarms as a requirement in the standard had been discussed since the standard was first proposed with debate focused on the unreliability and cost of alarms.
Francisco said the committee believes the time has come to make this change, noting that it brings the standard into closer alignment with the International Residential Code, which requires alarms if the house has combustion appliances or attached garages, and with many states that have passed laws requiring CO alarms.
The requirement goes a step further, expanding the protection to all homes, regardless of fuel type or garage configuration, reflecting the fact that many CO exposures occur due to causes completely independent of these factors, he said. It also requires that alarms be hard-wired with battery backup to address an increased likelihood of high CO exposure events during power outages.
Other significant new changes include the removal of the climate limitations on pressurization and depressurization; specifications related specifically to multifamily buildings; and new calculations and weather data for estimating annual leakage based on a blower door test.
The cost of Standard 62.2-2013, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings, is $58 ($48, ASHRAE members).
To order, contact ASHRAE Customer Contact Center at 1-800-527-4723 (United States and Canada) or 404-636-8400 (worldwide), fax 678-539-2129, or visit www.ashrae.org/bookstore.
ASHRAE, founded in 1894, is a building technology society with more than 50,000 members worldwide. The Society and its members focus on building systems, energy efficiency, indoor air quality, refrigeration and sustainability within the industry. Through research, standards writing, publishing and continuing education, ASHRAE shapes tomorrow’s built environment today.
Related articles
- Article
ASHRAE 62.1-2013: Updated Ventilation Standard
ASHRAE Standard 62.1-2013 updates ventilation rates for commercial and institutional buildings. See the key changes from the 2010 edition and its 10 addenda.
- Article
New guidance for achieving enhanced IAQ now available from ASHRAE
New guidance for achieving enhanced IAQ is available from five leading building industry associations and the U.S. Environmental Protection Agency. The Indoor Air Quality Guide: Best Practices for Design, Construction and Commissioning is collaboration between ASHRAE, the American Institute of Architects, the Building Owners and Managers Association International, U.S. Environmental Protection Agency, the Sheet Metal and Air Conditioning Contractors of North America and the U.S. Green Building C
- Article
ASHRAE 62.1-2010 Ventilation Standard Explained
ASHRAE Standard 62.1-2010 sets minimum ventilation rates for commercial buildings. Learn the key changes to natural ventilation, exhaust, and IAQ rules.
- Article
ASHRAE 62.2-2010: Residential IAQ Standard
ASHRAE Standard 62.2-2010 sets ventilation requirements for low-rise homes. Learn what the residential IAQ standard covers and the 2010 retrofit changes.
- Article
ASHRAE Technology Awards: 2010 Winners
ASHRAE honored four standout building projects at its 2010 Winter Conference in Orlando, recognizing innovative, energy-efficient design.
- Article
IN 2013, RESNET TO JOIN ACCA, IAQA, RPA AT EXPO
Expanded Marketplace to Showcase Total Building Solutions for HVACR Contractors, IAQ Professionals, Energy Service Providers The Air Conditioning Contractors of America (ACCA), the Indoor Air Quality Association (IAQA), and the Radiant Professionals Alliance (RPA) will hold their combined 2011 Indoor Air Expo in San Antonio, Texas from February 15-17.But work has already begun on future events, and this week the three associations announced that, in 2013, they will be joined by the Residential E